Đầu báo lửa Honeywell. Model: FSL100

Model: UV (Ultraviolet) Flame Detector

UV flame detector. Suitable for ATEX zone 2/22; FM 3611 Class 1,2&3 Div2

EN54-10 (HIGH sensitivity) certificate FM3260 approval. Red Housing

Part Number: SL100-UV

 

42.500.000

Còn hàng
Mã: FSL100 Danh mục: Từ khóa: ,

Mô tả

Honeywell’s FSL100 range of Light Industrial/Commercial Flame Detectors enables simple coverage of fire hazard areas across many fire hazard applications. Installation, set-up and operation are simple. Wide solid area coverage and fast speed of response omtimize safety. With inbuilt automatic test and test lamps available to cover all models, reliability is ensured.

Product Overview:

The newest Optoelectronic flame detector for a wide range of Light Industrial fire detection from Honeywell Analytics.

A range of middle market Optical Flame Detectors joining the HA FSX High End products. Addresses a wide range of fire protection applications both indoors and outdoors. With 3 versions to cover a wide range of flaming fires: Ultraviolet (UV), Ultraviolet/Infrared (UV/IR) and Triple Infrared (IR3).

Detects wide range of Hydrocarbon & Non-Hydrocarbon firesDetecting a wide range of Hydrocarbon and Non-Hydrocarbon flaming fires means that many application areas can be addressed.

Wide viewing angle

Optical detection of radiant energy in a solid angle Field of View enables coverage of a large risk area. Simple optional mounting bracket allows the FSL100 to be installed and aligned covering the hazard.

Fast response

Far faster than other technologies, by responding to flaming fires in seconds enabling a more rapid response to danger before the fire can escalate.

FM Class1, 2 & 3 Div2

Can be installed indoors or outdoors and in Hazardous areas typically looking into a Div 1 area from a distance.

FM 3260 performance cert

Certified to FM 3260 for flame Detector performance.

Relay and current output (Fault and Alarm)

Analog stepped output and Alarm/Fault relays for simple connectivity.

Inbuilt Automatic Test and Simple to use Test Lamps

FSL100 maintains continuous internal health monitoring. Test lamps enable simple operational and Field of View testing.

Features & Benefits:

  • UV, UV/IR and IR3 Flame Detectors to cover a wide range of applications
  • Robust, simple to install & set-up: Wide angle and fast speed of response
  • Automatic test and test lamps for simple check and maintenance.

Quick Specs:

  • FSL100 Flame Detectors – UV, UV/IR and IR3 for light industrial applications
  • GRP Housing, available in Red or White with optional swivel mount
  • 12-14Vdc, 25mA nominal operation
  • 4 to 20mA and Relay outputs.

Tech Specs:

FSL100 Flame Detector Types  FSL100-UV
FSL100-IR3
FSL100-UVIR
Choice of red or white housings
Range FSL100-UV/25m
FSL100-IR3: 35m/110ft
FSL100-UVIR: 80ft alarming within 10 seconds to a 0.1m(1 ft2) n-heptane fire
Cone of Vision 90˚ minimum horizontal and vertical
Local LEDs Continuous green: normal operationContinuous yellow: faultFlashing yellow: fault and guide to repeat self-test after a self-test failureContinuous red: alarm
Current Output Standard available 4–20mA (stepped, sinking, non-isolated)0mA power fault/microprocessor fault2mA optical fault4mA normal operation>20mA alarm
Relay  Output:– Alarm relay– Fault relay De-energized during normal operation, no alarm, SPDT, 30VDC – 2A, 60W max. Energised during normal operation, nofault, SPDT, 30VDC – 2A, 60W max.
Cable Gland & Terminals Cable entry M20 clearance. Supplied with a gland suitable for cable diameter from 5.5mm (0.2”) to 13mm (0.5”). Terminalssuitable for 0.5mm2 (20AWG) to 1.5mm2 (15AWG) wire
Start up Times <10 sec
Alarm Response Time 8 to 30 sec
Alarm Output Settings Selectable LEDs and relays latching/non-latching; factory setting: latching
Automatic & Manual Self-Test Automatic sensor test (built in self-test) and manual self-test
Operating Current Normal 25mA at 24VDC
Current in Alarm, at 24 VDC ±75mA at 24VDC
Connections to Fire control panels using end-of-line (EOL) and alarm resistors (current increase)Devices that operate via relay switched outputsPLCs with 4–20mA inputs
End-of-Line and Alarm Resistor To be adjusted to the fire control panel; free terminals are dedicated to the resistors
Note: the alarm and EOL resistor must be rated 2W min. each and the total power dissipation of both alarm and EOLresistor should not exceed 2W
Housing Glass Reinforced Polyester (GRP), Non-incendive. UV resistant, Self-Extinguishing V–0 (UL-94)
Swivel Mount PA66, UV resistant; Stainless Steel fixings; 280g (0.62lb)
Pressure Compensating Element PCE (Pressure Compensating Element) avoids moisture build-up in the detector housing due to changes in ambient air pressure
Dimensions 125 x 80 x 57mm (4.9 x 3.15 x 2.25in )
Weight 465g (1.05lb)
Ingress Protection IP65
Temperature, Operating –40˚C to +70˚C (–40˚F to +158˚F )
Temperature, Ambient ATEX and FM Class 3611 –25˚C to +70˚C (–13˚F to +158˚F )